As per IS: 2190 ANNEX-E Schedule for Hydraulic Pressure testing of Fire Extinguishers | ||
---|---|---|
E-1 Every fire extinguisher installed in premises shall be hydraulically pressure tested as per schedule given below. There shall not be any leakage or visible distortion. Extinguisher which fails in these requirements shall be replaced |
S.No | Type of Fire Extinguishers | Test Interval Year | Test Pressure kg/cm² | Pressure Maintained for minutes |
---|---|---|---|---|
1. | Water type(gas cartridge) IS 940 | 3 | 35 | 2.5 |
2. | Water type(stored pressure) IS 6234 | 3 | 35 | 2.5 |
3. | Water type(gas cartridge) IS 13385 | 3 | 35 | 2.5 |
4. | Mechanical Foam(AFFF) Gas Cartridge IS 10204 | 3 | 35 | 2.5 |
5. | Mechanical Foam(AFFF) (Stored Pressure IS 15397 | 3 | 35 | 2.5 |
6. | Mechanical Foam(AFFF) Gas Cartridge ( Gas Cartridge) (IS 13386) | 3 | 35 | 2.5 |
7. | Mechanical Foam(AFFF) Gas Cartridge ( Gas Cartridge) 135liter (IS 14951) | 3 | 35 | 2.5 |
8. | Dry powder(stored pressure) IS 13849 | 3 | 35 | 2.5 |
9. | Dry powder type(DCP) IS 2171, IS 10658, IS 11833 | 3 | 35 | 2.5 |
10. | Clean Agent (IS 15683) | 3 | 35 | 2.5 |
11. | Carbon Di Oxide IS 2878 | 5 | 250 | 2.5 |
E-2 The Carbon dioxide (Co2) type and Halon 1211 type fire extinguishers shall be pressure tested every time the cylinders are sent for recharging(after periodic discharge test or otherwise) to the pressure specified in the relevant Indian Standard specifications. |
---|